Introduction Co-extrusion design,semi-conductive/insulation/elastomeric insulation tri-layer heat shrink tube.The elastomeric layer is designed to have a fast shrinkage rate to avoid overheating damage.Suitable for insulation protection of power cable...
Introduction
Co-extrusion design,semi-conductive/insulation/elastomeric insulation tri-layer heat shrink tube.The elastomeric layer is designed to have a fast shrinkage rate to avoid overheating damage.Suitable for insulation protection of power cable joint under 36kV.
Features
Operating temperature: -55 to 105°C
Minimum fully recovery temperature: 150°C
Voltage class: 6kV ~ 36kV
Halogen-free, RoHS compliant, Ultra heavy wall
Semi-conductive / insulation / Elastomeric Insulation Three-layer
Standard Color: Black (outer layer) / Red(inner layer)
Dimension
| Part No. C106 |
As supplied(mm) | After recovered(mm) | Standard | |||
| Inner diameter D(min.) |
Inner diameter d(max.) |
Wall thickness t(nom.) |
length (m/pc) |
|||
| 35/13 | 35 | 13 | 11.0 | ≤1.22 | ||
| 45/17 | 45 | 17 | 12.0 | ≤1.22 | ||
| 50/21 | 50 | 21 | 12.0 | ≤1.22 | ||
| 63/26 | 63 | 26 | 12.5 | ≤1.22 | ||
| 75/34 | 75 | 34 | 12.5 | ≤1.22 | ||
| 85/34 | 85 | 34 | 12.5 | ≤1.22 | ||
| 95/42 | 95 | 42 | 13.5 | ≤1.22 | ||
| 110/52 | 110 | 52 | 13.5 | ≤1.22 | ||
| 125/62 | 125 | 62 | 14.0 | ≤1.22 | ||
Technical Data
| Property | Test Method | Requirement | ||
| Outer Layer(Semi-Conductive,Black | ||||
| Tensile Strength | ASTMD 2671 | ≥12 MPa | ||
| Ultimate Elongation | ASTM D 2671 | ≥270% | ||
| Heat Aging(158°C/168h) | ASTM D 2671 | |||
| Tensile Strength | ≥10 MPa | |||
| Ultimate Elongation | ≥250% | |||
| Water absorption(23℃/24h) | ASTMD 2671 | ≤0.5% | ||
| Low-temperature flexibility(-40°℃/4h) | ASTM D2671 | No cracking | ||
| Heat shock(200°℃/4h) | ASTM D 2671 | No dripping or flowing | ||
| Volume resistivity | ASTMD 2671 | ≤1×10+Ω.cm | ||
| Middle Layer(Plastic Insulation,red) | ||||
| Tensile Strength | ASTM D 2671 | ≥12 MPa | ||
| Ultimate Elongation | ASTM D 2671 | ≥350% | ||
| Heat Aging(136°C/168h) | ASTM D 2671 | |||
| Tensile Strength | ≥10 MPa | |||
| Ultimate Elongation | ≥270% | |||
| Water absorption (23C/24h) | ASTM D 2671 | ≤0.5% | ||
| Low-temperature flexibility (-40°℃/4h) | ASTMD 2671 | No cracking | ||
| Heat shock(200°℃/4h) | ASTMD2671 | No dripping or flowing | ||
| Dielectric strength | ASTM D 2671 | ≥15kV/mm | ||
| Volume resistivity | ASTMD 2671 | ≥1×10¹³Ω.cm | ||
| Inner Layer(Elastomeric Insulation,red) | ||||
| Tensile Strength | ASTMD 2671 | ≥6MPa | ||
| Utimate Elongation | ASTM D 2671 | ≥270% | ||
| Heat Aging(136°C/168h) | ASTMD 2671 | |||
| Tensile Strength | ≥4.2 MPa | |||
| Ultimate Elongation | ≥200% | |||
| Water absorption (23C/24h) | ASTMD 2671 | ≤0.5% | ||
| Low-temperature flexibility(-40°℃/4h) | ASTMD 2671 | No cracking | ||
| Heat shock(200°℃/4h) | ASTM D 2671 | No dripping or flowing | ||
| Dielectric strength | ASTM D 2671 | ≥15kV/mm | ||
| Volume resistivity | ASTM D 2671 | ≥1×10¹³Q.cm | ||