Sold out

C101 Non-tracking Heat Shrink Tube

C101
$0.00
C101 Non-tracking Heat Shrink Tube Introduction Cross-linked polyolefin,with or without adhesive liner.Excellent resistance to electrical tracking and creeping corrosion.Suitable for insulation protection of indoor and outdoor power cable...
Tags:
C101 Non-tracking Heat Shrink Tube
Introduction
Cross-linked polyolefin,with or without adhesive liner.Excellent resistance to electrical tracking and creeping corrosion.Suitable for insulation protection of indoor and outdoor power cable terminations or joints.

Features
Operating temperature: -55 to 105°C
Minimum fully recovery temperature: 125°C
Voltage class: 6kV ~ 36kV
Halogen-free, RoHS compliant, Flame-retardant
Single or Dual wall optional
Shrink ratio: 2:1 & 3:1
Standard Color: Red, Other colors optional

Dimension
Part No.
C101
As supplied(mm)
Inner  diameter
D(min.)
After recovered(mm) Standard length
(m/pc or m/roll)
Inner diameter
  d(max.)
Wall thickness
t(nom.)
19-6 19  6  2.5  1.22/15
30-10 30  10  3.0  1.22/15
38-12 38  12  3.0  1.22/15
40/16 40  16  3.0  1.22/15
45/18 45  18  3.0  1.22/15
55/21 55  21  3.0  1.22/15
65/28 65  28  3.0  1.22/15
75/36 75  36  3.0  1.22 
85/40 85  40  3.2  1.22 
100/40 100  40  3.6  1.22 
130/50 130  50  3.7  1.22 

 

Technical Data

Property Test Method     Requirement
Tensile Strength ASTM D2671     ≥8MPa
Ultimate Elongation ASTM D2671     ≥200%
Secant modulus 2% ASTM D2671     ≤170 MPa
Heat Aging(150°℃/168h) ASTM D2671
Tensile Strength     ≥8MPa
Ultimate Elongation     ≥100%
Water absorption(23℃/24h) ASTM D2671     ≤0.5%
Low-temperature flexibility(-40°℃/4h) ASTM D2671     No cracking
Heat shock(200°℃/4h) ASTM D2671     No cracking,dripping or flowing
Dielectric strength ASTM D2671     ≥15kV/mm
Volume resistivity ASTM D2671     ≥1×10²Ω.cm
Tracking and erosion resistance ASTM D2303     After 1hrat 2.5kV,and 1hrat 2.75kV,
    and  1hr at  3.00kV,and 20mins at
    3.25kV.No    burn    penetration,no
    sustained burning
Flammability ASTM2863     Ol≥25
Color fastness to light IEC 60684-3     No visible change