Esgotado
C15-35 26/35(40.5)kV Heat Shrink Cable Accessories
C15-35
$0.00
Introduction Single core, three cores heat shrik cable accessories. Suitable for protection of indoor and outdoor electric power cable joint and termination under 26/35 kV. Features Voltage class:...
Introduction
Single core, three cores heat shrik cable accessories. Suitable for protection of indoor and outdoor electric power cable joint and termination under 26/35 kV.
Features
Voltage class: 26kV/35kV
Operating temperature: -55 to 105°C
Supplied by set, with the materials in the kit
Well resistance against weather and damage
Compliant Standard: IEC 60502-4:2010-12, GBT 12706.4
Dimensions
| Indoor Termination | Outdoor Termination | Joint | Size for | ||||
| PartNo. NSY |
Cable core num. |
Part No. WSY |
Cable core num. |
Part No. JSY |
Cable core num. |
conductor mm² |
|
| NSY-3531 | 3 | WSY-3531 | 3 | JSY-3531 | 3 | 25-50 | |
| NSY-3532 | 3 | WSY-3532 | 3 | JSY-3532 | 3 | 70-120 | |
| NSY-3533 | 3 | WSY-3533 | 3 | JSY-3533 | 3 | 150-240 | |
| NSY-3534 | 3 | WSY-3534 | 3 | JSY-3534 | 3 | 300-400 | |
| NSY-3511 | 1 | WSY-3511 | 1 | JSY-3511 | 1 | 25-50 | |
| NSY-3512 | 1 | WSY-3512 | 1 | JSY-3512 | 1 | 70-120 | |
| NSY-3513 | 1 | WSY-3513 | 1 | JSY-3513 | 1 | 150-240 | |
| NSY-3514 | 1 | WSY-3514 | 1 | JSY-3514 | 1 | 300-400 | |
Technical Data
| Test | Test methods | Requirements | |||||
| AC and DC Voltage | AC for 5min at 4.5U,or | Ambient temperature | |||||
| DC for 15min at 4U。 | No breakdown,No flashover | ||||||
| AC voltage (wet)(termination) | 1min at 4U₀ | No breakdown,No flashover | |||||
| AC voltage | 15min at 2.5U。 | No breakdown,No flashover | |||||
| Partial discharge | At 1.73U。 | 10 pC max. | |||||
| Impulse atθ |
10 impulses of each polarity θ;conductor's max.operating temp.plus5~10℃ |
No breakdown,No flashover | |||||
| Heating cycles in air | 60 cylces ate and 2.5U。 | No breakdown,No flashover | |||||
| Thermal short-circuit | two short-circuits to raise conducto toθ of the cable | No visible deterioration | |||||
| (conductor) | .:the specified short-circuit temp.of conductor | ||||||
| Dynamic short-circuit | One short-circuit atl I:the specified short-circuit lectricurent of conductor |
No visible deterioration | |||||
| Humidity(ndoortermination) | 300hrs at 1.25U。, | No breakdown, | |||||
| tripping not more than 3 times. | No visible deterioration | ||||||
| Salt fog(outdoor termination) | 300hrs at 1.25U。, | No breakdown, | |||||
| tripping not more than 3 times. | No visible deterioration | ||||||