Esgotado

Y3 Non-tracking Heat Shrink Rain Shed (Skirts)

Y3
$0.00
Introduction Cross-linked polyolefin,non-tracking,mastic applied to collars.Suitable for insulation of outdoor power cable termination. Features Operating temperature: -55 to 105°C Minimum fully recovery temperature: 150°C Voltage class: 1kV ~...
Tag:
Introduction
Cross-linked polyolefin,non-tracking,mastic applied to collars.Suitable for insulation of outdoor power cable termination.

Features
Operating temperature: -55 to 105°C
Minimum fully recovery temperature: 150°C
Voltage class: 1kV ~ 36kV
Non-tracking, UV and weather resistance
Adhesive liner
Standard Color: Red

Customized Normal adhesive liner or Red adhesive liner on Request.
Dimension
Part No.
Y3
As supplied(mm)
Inner  diameter
D2(±10%)
After recovered(mm)
Inner diameter
D2(max.)
Diameter
D1(nom.)
H(min.) Wall thickness
  W(nom.)
30-12 30  12  95  18  3 
35/14 35  14  95  18  3 
45/19 45  19  120  20  3 
50/19 50  19  120  20  3 
60/23 60  23  130  20  3 
75/30 75  30  140  22  3 
110/50 110  50  175  28  3 
130/65 130  65  200  30  3 
160/80 168  80  245  30  3 
180/80 180  80  245  30 

3

 

Technical Data

Property Test Method   Requirement
Tensile Strength ASTMD 2671   ≥12MPa
Ultimate Elongation ASTMD 2671   ≥300%
Heat Aging(136°/168h) ASTM D 2671
Tensile Strength   ≥10 MPa
Ultimate Elongation   ≥200%
Water absorption(23°℃/24h) ASTMD 2671   ≤0.5%
Low-temperature flexibility(-40°℃/4h) ASTM D 2671   No cracking
Heat shock(200°℃/4h) ASTMD 2671   No dripping or flowing
Dielectric strength ASTMD2671   ≥15kV/mm
Volume resistivity ASTM D 2671   ≥1×10¹³Q.cm
Tracking and erosion resistance ASTMD2303   After 1hr at 2.5kV,and 1hr at 2.75kV,
  No  burn  penetration,no  sustained
  burning